FusionModule2000 Smart Modular Data Center
Installation Guide
15 Installing Monitoring Devices
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
182
Step 4 Connect the server power cables to the rPDU.
The server uses dual power supplies. Connect the two power cables to different rPDUs.
Figure 15-5 Connecting server power cables
----End
15.1.2 (Optional) Installing a VCN500
Preparations
Tool: Phillips screwdriver
Material: VCN500
Document: installation position diagram for monitoring devices in the network cabinet
Procedure
Step 1 Determine the mounting holes for a VCN500 based on the installation position diagram for
monitoring devices in the network cabinet, adjust the guide rails, and install floating nuts.