FusionModule2000 Smart Modular Data Center 
Installation Guide 
 
Huawei Proprietary and Confidential                                     
Copyright © Huawei Technologies Co., Ltd. 
 
17 Connecting Cables 
17.1 System Cabling Rules 
Attaching Cable Labels 
 
 
A cable label must be consistent with the corresponding IT cabinet number. 
 
Find the corresponding cable based on the wiring diagram in the cable fitting bag, and 
attach the corresponding cable label taken out from the cable fitting bag to both ends of 
the cable by wrapping the ends. 
 
The cable labels must completely wrap the cable without wrinkles. 
 
Attach the cable labels 20 mm away from the plug except for special circumstances. For 
example, a label shall not be attached to the bending part of a cable or attached in some 
positions that may affect cable installation. 
 
  If a label conflicts with a cable tie, attach the label to the outer side of the cable tie. 
 
Attach labels to both ends of a cable. 
Requirements for Neatly Routing and Binding Cables 
To route and bind cables in an appealing way, follow these rules: 
1.  Neatly organize exterior cables in a large bundle of cables and prevent cable tangles that 
are avoidable, as shown in Figure 17-1.