FusionModule2000 Smart Modular Data Center
Installation Guide
17 Connecting Cables
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
276
Ensure that strong-current cables and weak-current cables are at least 100 mm away from
each other.
Connect the power cables from the general input unit side to the smart module.
Figure 17-11 Routing power cables and network cables
(1) General input unit
(2) Power distribution unit
(3) Network cabinet
(4) Power cable
(5) Conversion unit
(6) Signal cable