Figure 7-31 Remove the xing plate of the magnetic lock
2. After the base and the xing plate are secured, route the magnetic lock cables
into the base and secure all the components.
3. Install a double-door magnetic lock by performing the operations prior to
Step 3 in a reverse order.
----End
Follow-up Procedure
If the electromagnet does not work properly after power-on, check the following
items:
1. Check whether the electromagnets provide magnetic force by attaching
magnetizable iron parts to them.
2. Check whether the magnetic iron plates align with the electromagnets.
3. Check whether gaps exist between the magnetic iron plates and the
electromagnets.
If any of the preceding conditions occur, troubleshoot the magnetic lock as
follows:
1. Check the circuit and rectify any circuit fault.
2. Adjust the magnetic iron plate base and door panels to ensure that the
magnetic iron plates align with the electromagnets. Ensure that the position
deviation is no too large.
3. If gaps exist between the electromagnets and the magnetic iron plates, rectify
the fault by referring to Figure 7-32.
4. If the magnetic iron plates are not level with each other, adjust them by using
the spacer shown in Figure 7-33.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center) 7 Device Maintenance
Issue 02 (2021-05-12) Copyright © Huawei Technologies Co., Ltd. 310

Table of Contents

Related product manuals