EasyManua.ls Logo

JUMO LOGOSCREEN 601 - Page 160

JUMO LOGOSCREEN 601
280 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Configuration
160
Example of tolerance band monitoring
The principle of the alarm follows the alarm configuration of the individual analog channels.
Channel 1: Measured value = 21°C (reference value)
Upper tolerance band limit = 10°C
Upper switching differential = -2°C
Channel 2: Tolerance band is active.
The alarm is generated if the current measured value from channel 2 is above 31 °C.
The alarm is canceled again if the current measured value drops below 29 °C.
Channel 1: Measured value = 21°C (reference value)
Lower tolerance band limit = -10°C
Lower switching differential = 2°C
Channel 2: Tolerance band is active.
The alarm is generated if the current measured value from channel 2 is below 11 °C.
The alarm is deleted again if the current measured value exceeds 13 °C.
NOTE!
In the example shown, channel 1 is constant and channel 2 changes its measured value. This does not
have to be the case. It could just as easily be channel 1 that changes, or even both channels.
(1) Lower alarm 1 Alarm on
(2) Upper alarm 0 Alarm off
(3) Switching differential
(1)
(2)
(3)
(3)
1
0

Table of Contents

Other manuals for JUMO LOGOSCREEN 601

Related product manuals