7 Configuration
7.24 Time settings
The settings in this dialog are used to synchronize multiple devices by means of a control signal.
NOTE!
The date and time are set in the device parameterization or setup program (online parameters). The PC's
date and time are used for the settings in the setup program. The date and time can also be set using a
time server.
Device dialog box
Parameter
Control signal for time sync
The signal is used to synchronize multiple devices. The time is synchronized when transferring from Low
to High (min. pulse duration = 125 ms). The seconds are crucial to changing the time. The time is put
forward or back by a maximum of ±30 seconds. Example:
12:55:29 -> 12:55:00, 12:55:30 -> 12:56:00
NOTE!
In the setup program, the time zone and daylight saving time are also set during the configuration; in the
device, they are set in the parameterization (Parameterization > Date and time).
Parameter Selection/settings Description
Control signal for
time sync
Digital selector
No selection
Control signal for synchronizing the time
(with low-high edge)
Sync during batch No, Yes If "Yes", the time can also be synchro-
nized while batch reporting is in prog-
ress.
?

Table of Contents

Other manuals for JUMO LOGOSCREEN 601

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the JUMO LOGOSCREEN 601 and is the answer not in the manual?

JUMO LOGOSCREEN 601 Specifications

General IconGeneral
BrandJUMO
ModelLOGOSCREEN 601
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals