NICE1000
new
User Manual Function Code Table
- 97 -
Function
Code
Parameter Name Setting Range Default Unit
Property
Fb-16
Door lock waiting time
at manual door
0–50 0 s
Fb-17
Holding time for forced
door close
5–180 120 s
Group FC: Protection Function Parameters
FC-00
Program control for
protection function
0–65535
Bit0: Short-circuit to ground
detection at power-on
Bit1: Canceling current
detection at inspection startup
Bit2: Decelerating to stop at
valid light curtain
Bit3: Password ineffective
if no operation within 30
minutes
Bit4–Bit9: Reserved
0 -
FC-01
Program control 2 for
protection function
0–65535
Bit0: Overload protection
Bit1: Canceling protection at
output phase loss
Bit2: Canceling over-
modulation
Bit3: Reserved
Bit4: Light curtain judgment at
door close limit
Bit5: Canceling SPI
communication judgment
Bit7:Reserved
Bit8:Reserved
Bit9: Canceling Err55 alarm
Bit10–Bit13: Reserved
Bit14: Canceling protection at
input phase loss
1 -
FC-02
Overload protection
coefcient
0.50–10.00 1.00 -
FC-03
Overload pre-warning
coefcient
50–100 80 %