A-10 Fieldbuses
AC30 series Variable Speed Inverter
Modbus Conn Timeout
1458 Setup::Communications::Base Modbus
Parameters::Base Comms::Modbus
66 seconds 0 – 100,000 seconds ALWAYS
Modbus TCP parameter.
Sets the Modbus connection timeout. If this parameter is set to zero then the connection will not timeout.
Modbus Mapping
1567 Setup::Communications::Base Modbus
Parameters::Base Comms::Modbus
none 0
Last parameter number
ALWAYS
Modbus TCP parameter.
User-defined Modbus parameter mapping table. Each entry in the table represents the required parameter
Mapping Valid
1632 Monitor::Communications::Base Modbus
Parameters::Base Comms::Modbus
TRUE FALSE
TRUE
NEVER
Modbus TCP parameter.
Status of the user defined mapping area. This will be set to TRUE if all entries in the mapping table are valid.
1659 Setup::Communications::Base Modbus
Parameters::Base Comms::Modbus
0000 0000
FFFF
ALWAYS
Modbus TCP parameter.
Modbus password. When set to a value other than zero, write access to parameters via the fixed mapping
registers will be restricted. To unlock the password, write to the Modbus register 00518 the value set in this
password. A subsequent write of value 0000 to Modbus register 00518 will lock the password.