C-234 Parameter Reference
AC30 series Variable Speed Drive
Parameters Defined in the Firmware
PNO
Name
Path
Type
Default
Range
Units
WQ
View
Notes
MBus
0001
Anin 01 Type
Setup::Inputs and Outputs::Base IO
Parameters::Inputs And Outputs::IO Configure
USINT
(enum)
0
0:-10..10 V
1:0..10 V
2:0..20 mA
3:4..20 mA
ALWAYS
OPERATOR
00529
0002
Anin 02 Type
Same as PNO 1
USINT
(enum)
0
0:-10..10 V
1:0..10 V
ALWAYS
OPERATOR
00531
0003
Anout 01 Type
Same as PNO 1
USINT
(enum)
0
0:-10..10 V
1:0..10 V
4:TORQUE OUT -10..10 V
ALWAYS
OPERATOR
00533
0004
Anout 02 Type
Same as PNO 1
USINT
(enum)
1
1:0..10 V
2:0..20 mA
3:4..20 mA
ALWAYS
OPERATOR
00535
0005
Digin Value
Monitor::Inputs and Outputs
Parameters::Inputs And Outputs::IO Values
WORD
(bitfield)
0:Digin 01
1:Digin 02
2:Digin 03
3:Digin 04
4:Digin 05
5:Digin 06
6:Digin 07
7:STO Inactive
8:Digin 11
9:Digin 12
10:Digin 13
11:Digin 14
12:Run Key
13:Not Stop Key
14:Stop Key
NEVER
OPERATOR
00537
0006
Digin Value.Digin 01
Same as PNO 5
BOOL
NEVER
OPERATOR
00539
0007
Digin Value.Digin 02
Same as PNO 5
BOOL
NEVER
OPERATOR
00541
0008
Digin Value.Digin 03
Same as PNO 5
BOOL
NEVER
OPERATOR
00543
0009
Digin Value.Digin 04
Same as PNO 5
BOOL
NEVER
OPERATOR
00545
0010
Digin Value.Digin 05
Same as PNO 5
BOOL
NEVER
OPERATOR
00547
0011
Digin Value.Digin 06
Same as PNO 5
BOOL
NEVER
OPERATOR
00549
0012
Digin Value.Digin 07
Same as PNO 5
BOOL
NEVER
OPERATOR
00551
0013
Digin Value.STO Inactive
Same as PNO 5
BOOL
NEVER
OPERATOR
00553
0014
Digin Value.Digin 11
Same as PNO 5
BOOL
NEVER
OPERATOR
00555
0015
Digin Value.Digin 12
Same as PNO 5
BOOL
NEVER
OPERATOR
00557
0016
Digin Value.Digin 13
Same as PNO 5
BOOL
NEVER
OPERATOR
00559
0017
Digin Value.Digin 14
Same as PNO 5
BOOL
NEVER
OPERATOR
00561
0018
Digin Value.Run Key
Same as PNO 5
BOOL
NEVER
OPERATOR
00563
0019
Digin Value.Not Stop Key
Same as PNO 5
BOOL
NEVER
OPERATOR
00565
0020
Digin Value.Stop Key
Same as PNO 5
BOOL
NEVER
OPERATOR
00567
0022
Digout Value
Same as PNO 5
WORD
(bitfield)
0000
0:Digout 01
1:Digout 02
2:Digout 03
3:Digout 04
4:Relay 01
5:Relay 02
8:Digout 11
9:Digout 12
10:Digout 13
11:Digout 14
14:Relay 11
15:Relay 12
ALWAYS
OPERATOR
2
00571
0023
Digout Value.Digout 01
Same as PNO 5
BOOL
FALSE
ALWAYS
OPERATOR
2
00573
0024
Digout Value.Digout 02
Same as PNO 5
BOOL
FALSE
ALWAYS
OPERATOR
2
00575
0025
Digout Value.Digout 03
Same as PNO 5
BOOL
FALSE
ALWAYS
OPERATOR
2
00577
0026
Digout Value.Digout 04
Same as PNO 5
BOOL
FALSE
ALWAYS
OPERATOR
2
00579
0027
Digout Value.Relay 01
Same as PNO 5
BOOL
FALSE
ALWAYS
OPERATOR
2
00581
0028
Digout Value.Relay 02
Same as PNO 5
BOOL
FALSE
ALWAYS
OPERATOR
2
00583
0031
Digout Value.Digout 11
Same as PNO 5
BOOL
FALSE
ALWAYS
OPERATOR
2
00589
0032
Digout Value.Digout 12
Same as PNO 5
BOOL
FALSE
ALWAYS
OPERATOR
2
00591
0033
Digout Value.Digout 13
Same as PNO 5
BOOL
FALSE
ALWAYS
OPERATOR
2
00593
0034
Digout Value.Digout 14
Same as PNO 5
BOOL
FALSE
ALWAYS
OPERATOR
2
00595
0037
Digout Value.Relay 11
Same as PNO 5
BOOL
FALSE
ALWAYS
OPERATOR
2
00601

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?

Parker AC30 series Specifications

General IconGeneral
Control ModesClosed-loop vector
FeedbackEncoder
Operating Temperature0 to 40°C (32 to 104°F) standard, -20 to 50°C (-4 to 122°F) with derating