9-4 Fire Mode
AC30 series Variable Speed Drive
Trips and Auto Restart
The following table summarizes which trips are disabled in the two modes of operation. Also shown are those trips which are designed to protect
the drive.
ID
Trip Name
Disabled in Partial mode
Disabled in Full mode
Drive Protection
1
OVER VOLTAGE
2
UNDER VOLTAGE
(1)
Note 1
Note 1
3
OVER CURRENT
4
STACK FAULT
5
STACK OVER CURRENT
6
CURRENT LIMIT
7
MOTOR STALL
8
INVERSE TIME
9
MOTOR I2T
10
LOW SPEED I
11
HEATSINK OVERTEMP
12
AMBIENT OVERTEMP
13
MOTOR OVERTEMP
14
EXTERNAL TRIP
15
BRAKE SHORT CCT
16
BRAKE RESISTOR
17
BRAKE SWITCH
18
LOCAL CONTROL
19
COMMS BREAK
20
LINE CONTACTOR
21
PHASE FAIL
22
VDC RIPPLE
23
BASE MODBUS BREAK
24
24V OVERLOAD
25
PMAC SPEED ERROR
Caution Disabling the Drive Protection trips will invalidate the drive’s warranty. Selecting PARTIAL mode leaves the drive protection features
enabled. Selecting FULL mode disables some of the drive protection features.
Caution Regardless of the setting of Level, activating Fire Mode may cause damage to the motor or attached equipment.