Parameter Reference C-205
AC30 series Variable Speed Drive
Spd Loop Settings
Parameters::Motor Control::Spd Loop Settings
This function block controls the speed of the motor by comparing the actual speed to the demanded speed, and applying more or less torque in
response to the error.
Only applies to SVC control mode, IM or PMAC.
Parameter Name
No.
Path
Default
Range
Units
Writable
Speed Loop Auto Set
1246
Parameters::Motor Control::Spd Loop
Settings
TRUE
ALWAYS
Only for PMAC Motor
TRUE : Allows to automatically calculate speed loop control parameters : Speed Loop Pgain and Speed Loop I Time.
To do a correct estimation, Ratio Load Mot Inert should be correctly filled in.
FALSE : no automatic calculation
Ratio Load Mot Inert
1247
Parameters::Motor Control::Spd Loop
Settings
1.0
0.1 to 100.0
ALWAYS
Only for PMAC Motor
Enter the correct inertia ratio between the load and the motor (For a no load condition, a value of 0.1 should be used).
This is used to automatically estimate the correct Speed Loop Pgain and Speed Loop I Time.
Speed Loop Bandwidth
1248
Parameters::Motor Control::Spd Loop
Settings
1
0:LOW
1:MEDIUM
2:HIGH
ALWAYS
Only for PMAC Motor
When Speed Loop Auto Set is TRUE, allows to select the speed loop bandwidth level :
Low :provides a low speed loop bandwidth
Medium : provides a medium speed loop bandwidth
High : provides a high speed loop bandwidth