A-52 Fieldbuses
AC30 series Variable Speed Inverter
Parameter Summary
Setup::Communications::Base PROFINET
Parameters::Base Comms::PROFINET IO Device
PROFINET IO parameter.
Enables the built-in PROFINET IO Device.
Setup::Communications::Base PROFINET
Parameters::Base Comms:: PROFINET IO Device
Enables the FIELDBUS BREAK trip on loss of connection.
Enumerated values:
the inverter will trip on the loss of connection to the PLC
Setup::Communications::Base PROFINET
Parameters::Base Comms:: PROFINET IO Device
Determines the IP address after PROFINET is enabled or the AC30 is power-cycled.
If set to FALSE then the behaviour is that of the PROFINET standard and the IP address will be set to zero if the IP address were
previously set by DCP with the temporary setting.
If set to TRUE then the IP address will be the last IP address set.
Setup::Communications::Base PROFINET
Parameters::Base Comms:: PROFINET IO Device
0: LITTLE ENDIAN
1: BIG ENDIAN
Sets the endian type for acyclic read and write requests of AC30 parameters. This does not apply to the cyclic I/O data which is
always Big Endian.
Enumerated values:
The least significant byte (LSB) of the data is sent first.
The most significant byte (MSB) of the data is sent first.
Monitor::Communications::Base PROFINET
Parameters::Base Comms::PROFINET IO Device
PROFINET IO parameter.
Indicates the PROFINET device Station Name. Only the first 21 characters are displayed.