A-52 Fieldbuses
AC30 series Variable Speed Inverter
Parameter Summary
Parameter Name
No.
Path
Default
Range
Writable
PROFINET Enable
3132
Setup::Communications::Base PROFINET
Parameters::Base Comms::PROFINET IO Device
FALSE
FALSE
TRUE
CONFIG
PROFINET IO parameter.
Enables the built-in PROFINET IO Device.
PROFINET Trip
3133
Setup::Communications::Base PROFINET
Parameters::Base Comms:: PROFINET IO Device
ENABLED
0: DISABLED
1: ENABLED
CONFIG
PROFINET IO parameter.
Enables the FIELDBUS BREAK trip on loss of connection.
Enumerated values:
0: DISABLED
the trip is disabled
1: ENABLED
the inverter will trip on the loss of connection to the PLC
PROFINET Use Drive
IP
3134
Setup::Communications::Base PROFINET
Parameters::Base Comms:: PROFINET IO Device
FALSE
FALSE
TRUE
CONFIG
PROFINET IO parameter.
Determines the IP address after PROFINET is enabled or the AC30 is power-cycled.
If set to FALSE then the behaviour is that of the PROFINET standard and the IP address will be set to zero if the IP address were
previously set by DCP with the temporary setting.
If set to TRUE then the IP address will be the last IP address set.
PROFINET Acyclic
Endn
3135
Setup::Communications::Base PROFINET
Parameters::Base Comms:: PROFINET IO Device
BIG ENDIAN
0: LITTLE ENDIAN
1: BIG ENDIAN
WRITABLE
PROFINET IO parameter.
Sets the endian type for acyclic read and write requests of AC30 parameters. This does not apply to the cyclic I/O data which is
always Big Endian.
Enumerated values:
0: LITTLE ENDIAN
The least significant byte (LSB) of the data is sent first.
1: BIG ENDIAN
The most significant byte (MSB) of the data is sent first.
PROFINET Station
Name
3136
Monitor::Communications::Base PROFINET
Parameters::Base Comms::PROFINET IO Device
-
-
NEVER
PROFINET IO parameter.
Indicates the PROFINET device Station Name. Only the first 21 characters are displayed.

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?