EasyManua.ls Logo

Parker AC30 series - Speed Error Trip

Parker AC30 series
462 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Reference C-209
AC30 series Variable Speed Drive
Speed Error Trip
Parameters::Trips::Speed Error Trip
This function allows the user to program the response of the drive in a situation where persistent speed error (as a difference between setpoint and
actual measured or estimated speed) occurs.
Parameter Name
No.
Path
Default
Range
Units
Writable
Speed Error Trip Enable
1746
Parameters::Trips::Speed Error Trip
TRUE
ALWAYS
A boolean that enables the speed error trip.
Speed Error Threshold
1747
Parameters::Trips::Speed Error Trip
50.00
0.00 to 100.00
%
ALWAYS
Level of speed error required to trigger the trip.
Speed Error Trip Delay
1748
Parameters::Trips::Speed Error Trip
10.000
0.000 to 2000.000
s
ALWAYS
Time period after which the drive trips. After half of this time a warning is issued.
Functional Description
If the difference between the setpoint and the actual motor speed is greater than a level defined in parameter 1747 (Speed Error Threshold)
for a period longer than time defined in parameter 1748 (Speed Error Trip Delay), the drive will trip. After half of that period a warning will be
produced. This is only operational if enabled via parameter 1746 (Speed Error Trip Enable).
.

Table of Contents

Other manuals for Parker AC30 series

Related product manuals