C-102 Parameter Reference
AC30 series Variable Speed Drive
IO Values
Monitor::Inputs and Outputs
Parameters::Inputs and Outputs::IO Values
These parameters present the Input and Output values in a form suitable for processing by the application and fieldbus.
Parameter Name
No.
Path
Default
Range
Units
Writable
Digout Value
0022
Monitor::Inputs and Outputs
Parameters::Inputs And Outputs::IO
Values
0000
0:Digout 01
1:Digout 02
2:Digout 03
3:Digout 04
4:Relay 01
5:Relay 02
8:Digout 11
9:Digout 12
10:Digout 13
11:Digout 14
14:Relay 11
15:Relay 12
ALWAYS
Presents all the digital outputs from the drive as a 16-bit word. The bits within the word may be accessed individually, or the entire
word may be accessed as a group.
Bit
Signal Name
Terminal
Comment
PNO for individual bit access
0
Digital Output 01
X12.1
Common terminal with digital input 4
0023
1
Digital Output 02
X12.2
Common terminal with digital input 5
0024
2
Digital Output 03
X12.3
Common terminal with digital input 6
0025
3
Digital Output 04
X12.4
Common terminal with digital input 7
0026
4
Relay 01
X14.1&2
0027
5
Relay 02
X14.3&4
0028
8
Digital Output 11
X20.1
GPIO option
0031
9
Digital Output 12
X20.2
GPIO option
0032
10
Digital Output 13
X20.3
GPIO option
0033
11
Digital Output 14
X20.4
GPIO option
0034
14
Relay 11
X23.1 & 2
GPIO option
0037
15
Relay 12
X23.3 & 4
GPIO option
0038