C-150 Parameter Reference 
AC30 series Variable Speed Drive 
Power Loss Ride Thru 
Parameters::Motor Control::Power Loss Ride Thru 
 
The block controls the behaviour of the drive during a power outage. 
When enabled, the drive attempts to keep the dc link high by regeneratively recovering the kinetic energy in the motor load in the event of a main 
power supply loss. 
 
Pwrl Enable 
 
1645 
 
Parameters::Motor Control::Power Loss 
Ride Thru 
FALSE 
 
STOPPED 
 
Enable the Power Loss Ride Through feature. 
Pwrl Trip Threshold 
 
1646 
 
Parameters::Motor Control::Power Loss 
Ride Thru 
52.0 
 
20.0 to 60.0 
 
% 
 
STOPPED 
 
Determines the dc link volts at which the Power Loss Ride Through sequence is triggered. 
% of the max dc link voltage ( drive overvoltage level = 100% ) 
Pwrl Control Band 
 
1647 
 
Parameters::Motor Control::Power Loss 
Ride Thru 
2.0 
 
0.0 to 20.0 
 
% 
 
STOPPED 
 
Determines the band while the speed setpoint is ramped down. 
% of the max dc link voltage ( drive overvoltage level = 100% ) 
Once the dclink falls down below Pwrl TripThreshold, the speed septoint is ramped to zero until the dc link rises above Pwrl trip 
Threshold + Pwrl Control Band.  
Then the speed septoint is hold, waiting either to continue ramping down if the dc link is still moving down or ramped back to the speed 
septoint if the supply returns. 
Pwrl Accel Rate 
 
1648 
 
Parameters::Motor Control::Power Loss 
Ride Thru 
100 
 
1 to 500 
 
Hz/s 
 
STOPPED 
 
Rate in Hz/s ( electrical frequency/ second) at which the speed septoint is ramped back to the speed demand