A-32 Fieldbuses
AC30 series Variable Speed Inverter
PROFINET IO Device
Introduction
The built-in PROFINET IO device (slave) is implemented in the AC30P/D inverters.
Features
The following PROFINET IO features are implemented:
• Minimum cyclic update time of 8ms
• Up to 64 slots
• Input mapping of up to 32 inverter parameters
• Output mapping of up to 32 inverter parameters
• Access of inverter parameters via read and write records
• Local or DCP address assignment
Identity
The PROFINET IO device has the following identity:
Vendor ID: 0x010F
Vendor Name: Parker Hannifin
Product Code 0xAC30
To make use of this feature, firmware version V4.x.x needs to be installed in the inverter. The firmware may be updated by downloading the
firmware file from the Parker website (see section Firmware Update in Chapter 4) or installed from the latest version of PDQ. With version
V4.x.x firmware installed, the AC30PNIO CoDeSys (PDQ/PDD) device is required.
Note: V4.x.x firmware has no AFE support and an application size of 96Kbytes (rather than 192Kbytes). The switching frequency is limited to
10kHz for induction motor control and 8kHz for PMAC motor control.