Parameter Reference C-199
AC30 series Variable Speed Drive
Slip Compensation
Parameters::Motor Control::Slip Compensation
Designed for VOLTS/Hz motor Control Mode.
The slip compensation function allows the Drive to maintain motor speed in the presence of increased load.
Parameter Name
No.
Path
Default
Range
Units
Writable
Slip Compensatn Enable
0354
Parameters::Motor Control::Slip
Compensation
FALSE
ALWAYS
Enable/Disable slip compensation
SLP Motoring Limit
0356
Parameters::Motor Control::Slip
Compensation
150
0 to 600
RPM
ALWAYS
Maximum compensated speed in motor control
SLP Regen Limit
0357
Parameters::Motor Control::Slip
Compensation
150
0 to 600
RPM
ALWAYS
Maximum compensated speed in regen mode
Functional Description
Based on the rated speed, the no load speed and the rated load of the motor, the Slip Compensation feature adjusts the demand frequency to
compensate for any speed reduction resulting from the load.

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?

Parker AC30 series Specifications

General IconGeneral
Control ModesClosed-loop vector
FeedbackEncoder
Operating Temperature0 to 40°C (32 to 104°F) standard, -20 to 50°C (-4 to 122°F) with derating
ProtectionOvercurrent, Overvoltage, Undervoltage
CommunicationRS485

Related product manuals