Trips & Fault Finding 7-11
AC30 series Variable Speed Inverter
Autotune Alerts
If the autotune fails to complete for any reason, an alert will be displayed and the autotune abandoned. Alerts are as follows:
The autotune has attempted to determine the leakage
inductance of the motor, but cannot make the required
Problem with motor connection.
The autotune is trying to find the encoder direction by
spinning the motor, but the motor is already spinning.
Wait till the motor stops.
Autotune has calculated a negative slip frequency,
which is not valid. Nameplate rpm may have been set
to a value higher than the base speed of the motor.
Check nameplate rpm, base frequency, and pole pairs are
correct.
The calculated value of rotor time constant is too large.
Check the values of Nameplate Speed and Base Frequency.
The calculated value of rotor time constant is too small.
Check the values of Nameplate Speed and Base Frequency.
During Autotune the motor is required to run at the
nameplate speed of the motor. If 100% Speed in RPM
parameter limits the speed to less than this value, an
Increase the value of 100% Speed in RPM parameter up to
the nameplate rpm of the motor (as a minimum). It may be
reduced, if required, after the Autotune is complete.
The autotune will compensate for low supply volts,
down to 70% of motor rated volts. Below this value it
will stop the autotune and raise an alert.
Re-try when mains volts are within specification.
The motor was unable to reach the required speed to
carry out the Autotune.
Possible reasons include: motor shaft not free to turn; the
motor data is incorrect.
It was not possible to find a suitable value of
magnetising current to achieve the required operating
Check the motor data is correct, especially nameplate rpm
and motor volts. Also check that the motor is correctly
Ke value calculated during the autotune (stationary) is
too large (the max value is 840V)
Check the motor data is correct, especially nameplate rpm,
rated amps and motor volts.
If low speed motor with a Ke value higher than 840V, enter
by hand the corresponding value after the autotune
Ke value calculated during the
autotune (stationary) is
too small (the min value is 1V)
Check the motor data is correct, especially nameplate rpm,
rated amps and motor volts.
All auto tune tests are disabled
Check parameter 0257: Autotune Test Disable