C-210 Parameter Reference
AC30 series Variable Speed Drive
Speed Ref
Parameters::Motor control::Speed Ref
This function holds all the parameters concerning the generation of the setpoint reference (reference ramp, speed trim, setpoint reverse, etc.).
Parameter Name
No.
Path
Default
Range
Units
Writable
Min Speed Clamp
1264
Parameters::Motor Control::Speed Ref
-110.00
-110.00 to 0.00
%
ALWAYS
Minimum value for Ramp Speed Output
Max Speed Clamp
1265
Parameters::Motor Control::Speed Ref
110.00
0.00 to 110.00
%
ALWAYS
Maximum value for Ramp Speed Output
Speed Trim
1266
Parameters::Motor Control::Speed Ref
0.00
-300.00 to 300.00
%
ALWAYS
The trim is added to the ramp output to form the Ramp Speed Output (unconditionally in remote mode).
In local mode, it is added is the Ref Trim Local parameter is set to TRUE
Trim in Local
1267
Parameters::Motor Control::Speed Ref
FALSE
ALWAYS
When TRUE, the trim is added to the ramp output in local mode.
When FALSE, the trim is not added to the ramp output in local mode.