C-118 Parameter Reference 
AC30 series Variable Speed Drive 
Motor Sequencer 
Parameters::Motor Control::Motor Sequencer 
 
These parameters are associated to the internal motor sequencer states machine to start and stop the motor control. 
 
Start Delay Enable 
 
1560 
 
Parameters::Motor Control::Motor 
Sequencer 
FALSE 
 
STOPPED 
 
Enable the delay to action “ramping to Setpoint” from the Run Command. This can allow a period for motor flux to establish ( AC 
induction motor ) before the ramp to setpoint 
Start Delay 
 
1634 
 
Parameters::Motor Control::Motor 
Sequencer 
0.000 
 
0.000 to 30.000 
 
s 
 
STOPPED 
 
Time to delay the action of “ramping to Setpoint” from the Run Command in seconds. 
Delay To Start 
 
1635 
 
Parameters::Motor Control::Motor 
Sequencer 
 
 
0.000 to Max 
 
s 
 
NEVER 
 
Remaining time of the delay  before “ ramping to Setpoint” after the Run Command occurs.