Parameter Reference C-69
AC30 series Variable Speed Drive
Feedbacks
Parameters::Motor Control::Feedbacks
The Feedbacks feature allows you to view speed feedback and motor current related diagnostics.
Parameter Name
No.
Path
Default
Range
Units
Writable
Duty Selection
0390
Setup::Motor Control::Control and Type
Parameters::Motor Control::Feedbacks
1
0:HEAVY DUTY
1:NORMAL DUTY
STOPPED
Heavy Duty ( typically 150%, 60s).
Normal Duty allowing higher continuous ratings with less overload capability ( typically 110%, 60s).
% are related to the Drive/stack ratings.
For example, a 12A drive ( @4kHz ) under Normal Duty becomes a 10A drive ( @4kHz) under Heavy Duty
DC Link Voltage
0392
Monitor::Motor and Drive
Monitor::Regen Control
Parameters::Motor Control::Feedbacks
x.
0 to 1000
V
NEVER
This shows the voltage across the dc link capacitors.
Actual Speed RPM
0393
Monitor::Motor and Drive
Parameters::Motor Control::
Feedbacks
x.xx
-100000.00 to 100000.00
RPM
NEVER
This parameter changes according to the Control Strategy:
In Vector Control mode the parameter shows the calculated mechanical speed of the motor shaft in rpm.
In Volts-Hertz Control mode the parameter shows motor synchronous speed in rpm.

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?

Parker AC30 series Specifications

General IconGeneral
Control ModesClosed-loop vector
FeedbackEncoder
Operating Temperature0 to 40°C (32 to 104°F) standard, -20 to 50°C (-4 to 122°F) with derating
ProtectionOvercurrent, Overvoltage, Undervoltage