EasyManuals Logo

Parker AC30 series User Manual

Parker AC30 series
462 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #342 background imageLoading...
Page #342 background image
C-160 Parameter Reference
AC30 series Variable Speed Drive
Ramp
Parameters::Motor Control::Ramp
This function forms part of the reference generation. It provides the facility to control the rate at which the Drive will respond to a changing setpoint
demand.
Parameter Name
No.
Path
Default
Range
Units
Writable
Seq Stop Method VHz
0484
Setup::Motor Control::Control and Type
Parameters::Motor Control::Ramp
1
0:DISABLED VOLTAGE
1:RAMP
2:STOP RAMP
3:DC INJECTION
ALWAYS
Volts/Hz control mode only
Selects stopping mode that the controller will use once the run command has been removed. The choices are:
Enumerated Value : Stopping Mode
Seq Stop Method SVC
1257
Setup::Motor Control::Control and Type
Parameters::Motor Control::Ramp
1
0:DISABLED VOLTAGE
1:RAMP
2:STOP RAMP
ALWAYS
All Control modes except Volts/Hz
Selects stopping mode that the controller will use once the run command has been removed. The choices are:
Enumerated Value : Stopping Mode
When DISABLED VOLTAGE ( COAST ) is selected the motor will free-wheel. When RAMP is selected the Drive will decelerate using
the reference ramp deceleration time, provided it is non-zero. When STOP RAMP is selected the motor will decelerate in Stop Ramp
Time.
Acceleration Time
0486
Same as PNO 484
10.000
0.000 to 3000.000
s
ALWAYS
The time that the Drive will take to ramp the setpoint from 0.00% to 100.00% when Ramp Type is LINEAR.
Deceleration Time
0487
Same as PNO 484
10.000
0.000 to 3000.000
s
ALWAYS
The time that the Drive will take to ramp the setpoint from 100.00% to 0.00% when Ramp Type is LINEAR.

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?

Parker AC30 series Specifications

General IconGeneral
Control ModesClosed-loop vector
FeedbackEncoder
Operating Temperature0 to 40°C (32 to 104°F) standard, -20 to 50°C (-4 to 122°F) with derating
ProtectionOvercurrent, Overvoltage, Undervoltage
CommunicationRS485

Related product manuals