PSRmodular system
120 / 232
PHOENIX CONTACT 109241_en_03
Frequency These fields display the calculated frequencies for the previously determined (switch-off)
threshold values (“fM”). The “fm” parameter, on the other hand, displays the restart value
(hysteresis). The set hysteresis applies for all threshold values.
If the displayed threshold value is GREEN, the result of the frequency calculation is positive.
If the displayed threshold value is RED, the parameters need to be modified.
Enable Error Out When this parameter is selected, an output (“E
RROR”) is made available which signals that
an error has been detected by the function block.
In the application program, this output is used to prevent startup after an error.
The hysteresis only needs to be modified if the following applies: fM = green; fm = red
1. Axis type:
Rotational
Sensor type:
Rotational
Frequency =
ƒ [Hz] =
Speed [rpm]
x Encoder resolution
[pulses/revolution]
60
2. Axis type:
Linear
Sensor type:
Rotational
Frequency =
ƒ [Hz] =
Speed [m/min] x 1000
x Encoder resolution
[pulses/revolution]
60 x Pitch [mm/revolu-
tion]
3. Axis type:
Linear
Sensor type:
Linear
Frequency =
ƒ [Hz] =
Speed [mm/s] x 1000
Encoder resolution
[µm/pulse]
Key
ƒ
Frequency
Encoder resolution Measured value
Speed [rpm] Revolutions per minute
Speed [m/min], [mm/s] Linear speed
Pitch Distance per revolution