PSRmodular system
176 / 232
PHOENIX CONTACT 109241_en_03
Duty cycle choice Up to seven inputs can be selected for seven different duty cycles of the output signal.
Depending on the active input, the clock signal has a corresponding duty cycle at “O
UT”.
The “I
N” input must always be set to logic “1”. The table below shows the method of opera-
tion of the “CLOCKING” operator.
Figure 5-149 Duty cycle examples for HIGH to LOW
Duty cycle
EN IN 10% IN 20% IN 30% IN 40% IN 60% IN 70% IN 80% OUT
0 0 0 0 0 0 0 0 0
1 0 0 0 0 0 0 0 50%
1 1 0 0 0 0 0 0 10%
1 0 1 0 0 0 0 0 20%
1 0 0 1 0 0 0 0 30%
1 0 0 0 1 0 0 0 40%
1 0 0 0 0 1 0 0 60%
1 0 0 0 0 0 1 0 70%
1 0 0 0 0 0 0 1 80%
1 1 0 0 0 0 0 1 90%
– To generate the desired clock signal at the “O
UT” output, the “EN” input and a clock
signal must be selected (controlled) at the “I
N x%” input.
– The clock signal generation for the 90% duty cycle can only be achieved through the
parallel control of both the “I
N 10%” input and the “IN 80%” input.
– If more than one clock signal input is controlled, the “O
UT” output generates a duty cy-
cle of 50% (exception: “I
N 10%” and “IN 80%”).
DUTY CYCLE 50%
DUTY CYCLE 20%
DUTY CYCLE 40%
DUTY CYCLE 80%
EN
Zeit