PSRmodular system
126 / 232
PHOENIX CONTACT 109241_en_03
Figure 5-80 Measured value representation with “Window comparator”
Enable threshold 1 /
Enable threshold 2
Figure 5-81 Parameters for the “Enable threshold 1” / “Enable threshold 2” options
The comparators for Threshold 1 and Threshold 2 operate independently of one another.
When the “Enable threshold x” option is selected, values need to be selected for the
“Threshold x” and “Hysteresis” parameters.
Key
UT Upper threshold
1
1
UT: Upper Threshold
UT - H Upper threshold - hysteresis
2
2
H: Hysteresis
LT Low threshold
3
3
LT: Low Threshold
LT - H Low threshold - hysteresis
0 Measured value outside the permissible range (status “O
UT”)
1 Measured value within the permissible range (status “O
UT”)
UT
UT - H
LT
LT - H
00 0 0 011 11