EasyManua.ls Logo

Phoenix Contact PSRmodular - Figure 5-144 DELAY LINE Operator; Figure 5-145: Time Diagram for DELAY LINE Operator

Phoenix Contact PSRmodular
236 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Items and operators of the PSRmodular Software
109241_en_03 PHOENIX CONTACT 173 / 232
Parameters
Threshold A threshold value between 0.5 s and 54915 s can be entered.
Scale 0.5 s ... 3000.0 s (in 0.5 s increments)
3005 s ... 52910 s (in 5 s increments)
5.4.5.7 DELAY LINE operator
This operator adds a delay to a signal and, in the event that the “I
N” signal is interrupted, it
sets the “O
UT” output to “0” after the entered time has elapsed. If the “IN” input is set to “1”
again within the set time, a logic “0” pulse occurs at the “O
UT” output for approximately two
cycles after the set time has elapsed.
Figure 5-144 “DELAY LINE” operator
Figure 5-145 Time diagram for “DELAY LINE” operator
Parameters
Time A delay between 10 ms and 1098.3 s can be entered.
Scale 0.01 s ... 60.0 s (in 10 ms increments)
60.1 s ... 1098.3 s (in 100 ms increments)
In contrast to the “DELAY” operator, the “DELAY LINE” operator does not filter any
interruptions in the “I
N” input that are shorter than the set time.
This operator is displayed when delayed outputs are used (the outputs must be pro-
grammed with “Manual Reset”).
OUT
IN
t
2 x Cycle time
OUT
IN
t

Table of Contents