Items and operators of the PSRmodular Software
109241_en_03 PHOENIX CONTACT 71 / 232
5.1.2 INPUT item
5.1.2.1 E-STOP function block (emergency stop)
The E-STOP function block checks the status of the “I
N” inputs of an emergency stop de-
vice. If the emergency stop button is pressed, the “OUT” output is logic “0”. Otherwise, the
output is logic “1”.
Figure 5-19 “E-STOP” function block (emergency stop)
Parameters
Input Type Single NC: enables the connection of a 1-channel emergency stop button.
Double NC: enables the connection of a 2-channel emergency stop button.
Manual Reset If this option is selected, a reset must be performed manually every time the function block
is activated. Otherwise, the activation of the output directly follows the state of the inputs.