Items and operators of the PSRmodular Software
109241_en_03 PHOENIX CONTACT 123 / 232
Figure 5-77 Measured value error for two-channel sensors
Incoherence calculation
mode
– Equal sensors (see Figure 5-76 on page 122): this option must be selected if the scale
is identical for both sensors. In this case, no additional parameters need to be config-
ured.
– Different sensors: this option must be selected if the scale is different for both sensors.
In this case, the scale of the second sensor must also be configured.
Key
S1, S2 Sensor measurement channel 1 and channel 2
D Error between the sensor measurements within the tolerance range
D
max
Maximum permissible error between the sensor measurements
DT
max
Maximum permissible duration of the error between the sensor measure-
ments outside the tolerance range
V Measured value
t Time