Items and operators of the PSRmodular Software
109241_en_03 PHOENIX CONTACT 147 / 232
5.4.2.6 MACRO MANUAL RESET
1
The “MACRO MANUAL RESET” operator enables the “Restart” to be triggered with param-
eterizable logic functions in accordance with the following truth table.
Figure 5-107 “MACRO MANUAL RESET” operator
Input Logic Enables the selection of the number of inputs for the Input logic (from 1 to 7). If 1 is selected,
the logic is not taken into consideration.
Select Logic Enables the selection of the operator type. Selection options: AND, NAND, OR, NOR, XOR,
XNOR.
Reset Input Logic Enables the selection of the number of inputs for the Reset logic (from 1 to 7). If 1 is selected,
the logic is not taken into consideration.
Reset Select Logic Enables the selection of the operator type for the Reset logic. Selection options: AND,
NAND, OR, NOR, XOR, XNOR.
Enable Clear If this option is selected, it is possible to reset storage.
1
Maximum number: 16 with PSR-M-B1, 32 with PSR-M-B2,
respectively including other reset operators
CLEAR
Out Input
logic
Out Restart
logic
OUT
Restart
Request
1 0/1 0/1 0 0
0/1 0 0/1 0 0
0 1 0 Initial value 0 1
0 1 Rising edge 1 0
0 1 Falling edge 1 0