PSRmodular Software: Basics
109241_en_03 PHOENIX CONTACT 53 / 232
Loading the configuration project (from the base module to the PC)
To load a project that is on the base module to the PSRmodular Software, use the icon
in the standard tool bar and await execution. The PSRmodular Software displays the project
that is present on the base module. The Level 1 password must be entered here.
Configuration log file
The log file is displayed with the icon in the tool bar (loading history).
Figure 4-15 Log file display
– If the uploaded project is to be used on a different PSRmodular system, check the
connected system configuration first.
– Then validate the project and perform a system test.
– The creation date as well as the CRC (in the form of four hexadecimal characters) are
saved in the configuration project.
– If the PSR-M-B2 base module is used, it is also indicated whether the source of load-
ing was the PSRmodular Software or PSR-M-MEMORY.
– The log file records a maximum of five events. As further events are recorded, the
register is overwritten starting with the oldest event.