Figure 5-168 Circuit diagram application example of the “NETWORK” function block for
category 2 (ISO 13849-1)
NOTE:
The RESET controlling devices must be installed outside of all danger zones, for example
at points where the danger zones and the entire working area are clearly visible.
A maximum of ten base modules can be networked.
Each base module may have a maximum of nine connected extension modules.
The maximum cable length between two base modules is 100 m.