Figure 5-5 “SINGLE/DUAL-OUTPUT” function block (safe output)
Parameters
Output Type Single
Dual
When using a PSR-M-B2, PSR-M-EF1 or PSR-M-EF5 module, the user can choose be-
tween various configurations:
1. 4 x SINGLE output (O) function block
2. 2 x DUAL output (O) function block
3. 2 x SINGLE output (O) function block + 1 x DUAL output (O) function block.
NOTE:
In order to achieve PL e and SIL 3 with single-channel wiring of the outputs, you must
rule out any errors in the cable installation for the control of the actuators (left illustra-
tion). Cross-circuits in the cable installation can be prevented in the same electrical
installation space or through mechanically protected cable installation.
If it is not possible to rule out errors, use two-channel wiring of the outputs (dual out-
put) for the control of the actuators.