Items and operators of the PSRmodular Software
109241_en_03 PHOENIX CONTACT 121 / 232
5.3 Analog function block
5.3.1 ANALOG INPUT function block
1
The function block enables the acquisition of single- or two-channel analog measured val-
ues (current or voltage). The function block enables the monitoring of up to two threshold
values as well as range monitoring.
Figure 5-73 ANALOG INPUT function blocks for
standard current signals (left)
and standard voltage signals (right)
Parameters
Input Type This parameter enables the selection of single- or two-channel
analog measured values.
Figure 5-74 “Single” input type (above) and
“Redundant” input type (below)
The “Single” input type enables the connection of a single-
channel sensor to one of channels 1 ... 4 of the PSR-M-EF7
extension module.
The “Redundant” input type enables the connection of a
two-channel sensor to adjacent channels (1 and 2 or 3 and 4)
of the PSR-M-EF7 extension module.
Figure 5-75 “ANALOG INPUT” parameter overview
1
Maximum number: 4 channels per PSR-M-EF7 expansion module