PSRmodular system
122 / 232
PHOENIX CONTACT 109241_en_03
When “Redundant” is configured as the input type, additional parameters need to be spec-
ified:
Figure 5-76 Additional parameters for “Redundant” input type
Sensors coherence (plau-
sibility check)
Allowed error: enables the specification of the permissible error between two channels
in a range from 0.1 .... 100.0 [...]. The error must not be greater than 10% of the defined
measuring range (e.g., 4 ... 20 mA --> 16 mA * 0.1 = 1.6 mA).
Error tolerance time (0.1 ... 2.5 s): maximum permissible duration in the event that the
specified error (“Allowed error”) is exceeded.