109241_en_03 PHOENIX CONTACT 169 / 232
Figure 5-135 Time diagram for “PASSING MAKE CONTACT” operator
Parameters
Time A delay between 10 ms and 1098.3 s can be entered.
Scale 0.01 s ... 60.0 s (in 10 ms increments)
60.1 s ... 1098.3 s (in 100 ms increments)
Retriggerable When this option is selected, the time is not reset on a falling edge at the input. The output
remains in the logic “1” state for the entire selected time. The timer is restarted on a new ris-
ing edge at the input.
Figure 5-136 Time diagram for “PASSING MAKE CONTACT” operator with activated
“Retriggerable” option
5.4.5.4 DELAY operator
The “DELAY” operator enables the “O
UT” output signal to be delayed by the parameterized
time value depending on the “I
N” input signal (switch-on delay or switch-off delay).
Figure 5-137 “DELAY” operator
Out
In
< T < T < T
T
Out
In
< T < T
T