Items and operators of the PSRmodular Software
109241_en_03 PHOENIX CONTACT 67 / 232
Figure 5-13 Example with external (left) and internal (right) relay
Category 2: outputs with category 2 single relays with OTE outputs. Each PSR-M-EF6
module can have up to four outputs of this type.
Output “O
TE” (Output Test Equipment) is logic 1” when no internal or external error is pres-
ent.
Properties:
Internal relays are always monitored.
Monitored EDM feedback.
Each output can be set: automatic, manual or manually monitored reset.
External K time monitoring” cannot be activated for a manual reset. On activation of the
“External K time monitoring” option, the “automatic” reset type (and therefore EDM
feedback) is activated automatically.
If you would like to use manual restart, there is a special logic for this. See note below
regarding “OTE”.
Figure 5-14 Outputs with category 2 single relays with “OTE” outputs
Key
KI Internal relay
KE External relay/contactor
Y External electromagnetically actuated valve
CAT4 CAT1 CAT1
M
VDC
KE1
M
VDC
KE4
KI1
MOR4
KI4
KI1 KE1PSR-M-B1
PSR-M-B1
VDC
AC/DC
KI1
MOR4
KI4
PSR-M-B1
CAT4 CAT1 CAT1
KI1 Y1PSR-M-B1
Y1
Y4