Items and operators of the PSRmodular Software
109241_en_03 PHOENIX CONTACT 127 / 232
The logic value output with output “OUT1” depends on the value of the active measurement
as well as the parameterized “Hysteresis”.
The entered “Hysteresis” must be in the range from 0.1 ... 6550.0 [...].
Assuming a measured value characteristic starts below “Threshold x”, switch on
(“O
UTx” = “1”) occurs when the value is > the parameterized value for “Threshold x”.
Subsequent switch off (“O
UTx” = “0”) then only occurs on an underrange of parameterized
“Threshold x” - “Hysteresis”.
Figure 5-82 Function example of the comparator with threshold
Key
T Threshold
1
1
T: Threshold
T - H Threshold - hysteresis
2
2
H: Hysteresis
0 Measured value below the threshold (status “OUT”)
1 Measured value above the threshold (status “O
UT”)
T
T - H
00 011