EasyManua.ls Logo

Phoenix Contact PSRmodular - Figure 5-148: CLOCKING Operator

Phoenix Contact PSRmodular
236 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Items and operators of the PSRmodular Software
109241_en_03 PHOENIX CONTACT 175 / 232
5.4.5.9 CLOCKING operator
This operator provides a clock signal at the output with the set period if the “I
N” input is at
logic “1”.
The “CLOCKING” operator has up to seven inputs for generating the duty cycle in the out-
put.
Figure 5-148 “CLOCKING” operator
Parameters
Time A time between 10 ms and 1098.3 s can be entered.
Scale 0.01 s ... 60.0 s (in 10 ms increments)
60.1 s ... 1098.3 s (in 100 ms increments)

Table of Contents