EasyManua.ls Logo

Phoenix Contact PSRmodular - Figure 5-132: Time Diagram for MONOSTABLE_B Operator When Rising Edge Parameter Is Selected; Figure 5-133: Time Diagram for MONOSTABLE_B Operator When Rising Edge Parameter Is Not Selected; Figure 5-134: PASSING MAKE CONTACT Operator

Phoenix Contact PSRmodular
236 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PSRmodular system
168 / 232
PHOENIX CONTACT 109241_en_03
Rising Edge If this parameter is selected, the “OUT” output is set to logic “1” on a rising edge at the “IN
input and remains in this state for the parameterized time, even in the event of a signal
change at the input.
Figure 5-132 Time diagram for “MONOSTABLE_B” operator when “Rising Edge” param-
eter is selected
If the “Rising Edge” parameter is deactivated, the logic is inverted. The “O
UT” output is set
to logic “0” as soon as a falling edge is detected at the “I
Ninput and remains in this state for
the parameterized time, even in the event of a signal change at the input.
Figure 5-133 Time diagram for “MONOSTABLE_B” operator when “Rising Edge” param-
eter is not selected
5.4.5.3 PASSING MAKE CONTACT operator
With this operator, the “O
UT” output is set to logic “1” on a rising edge at the “IN” input for as
long as the signal is present at the “I
N” input. At the latest, the “OUT” output is reset to logic
“0” after the parameterized time has elapsed.
Figure 5-134 “PASSING MAKE CONTACT” operator
Rising edge
Out
In
TT T
Falling edge
Out
In
TT T

Table of Contents