PSRmodular system
132 / 232
PHOENIX CONTACT 109241_en_03
Figure 5-88 Example circuit diagram for “Analog Output”
Enable Error Out
Figure 5-89 Function block for “Enable Error Out” option
When the “Enable Error Out” option is selected, the function block gets an additional “E
R-
ROR” output in the circuit diagram, which signals (logic “1”) that an error has been detected
by the function block.
Item Description A 24-character text description of the function or the name can be entered here. The text is
displayed above the function block.
NOTE:
In the event of an impermissible error between two channels (plausibility violation), the
value of the first channel will still be output at the “A
NALOG” output. In this case, the “ER-
ROR” output will be set to logic “1”.
Depending on the safety level to be achieved, you can additionally link the “E
RRORsignal
for further processing of the analog value in conjunction with analog operators.
NOTE:
Use the “E
RRORoutput depending on the safety level achieved in the circuit diagram (see
Figure 5-85 on page 130 and Figure 5-88 on page 132).
NOTE:
Perform a validation with subsequent test according to the connected sensors (e.g., scal-
ing).