Items and operators of the PSRmodular Software
109241_en_03 PHOENIX CONTACT 129 / 232
Minimum sampling rate
[Hz]
Current input Voltage input
Maximums signal frequency [Hz]
2,5 0,08 0,1
5 0,15 0,2
10 0,4 0,4
16 0,7 0,6
20 1,0 1
50 2,0 2
60 2,5 2
100 4,5 2
200 7,5 2
400 10,5 2
800 - 4000 11 2
Reaction time of the analog input function block relative to the sampling rate
Sampling rate [Hz] Maximimum reaction time [ms]
2,5 1200
5 600
10 300
16,6 240
20 200
50 80
60 80
100 60
200 50
400 - 4000 40
NOTE:
The overall accuracy must be taken into consideration when defining the limit values in
the application program.