PSRmodular system
142 / 232
PHOENIX CONTACT 109241_en_03
Operation (comparator) Depending on the value of the inputs and the selected operation, the following results are
achieved:
< Less than: the “O
UT” output is logic “1” as long as the value of the A inputs is below the
value of the B inputs. The “O
UToutput is set to logic “0” if the value of the A inputs is greater
than or equal to the value of the B inputs.
>= Greater than or equal to: the “OUToutput is logic “1” as long as the value of the A inputs
is above or equal to the value of the B inputs. The “O
UT” output is set to logic “0” if the value
of the A inputs is less than the value of the B inputs.
> Greater than: the “O
UToutput is logic “1” as long as the value of the A inputs is above the
value of the B inputs. The “O
UT” output is set to logic “0” if the value of the A inputs is less
than or equal to the value of the B inputs.
<= Less than or equal to: the “O
UT” output is logic 1” as long as the value of the A inputs is
below or equal to the value of the B inputs. The “O
UToutput is set to logic0” if the value of
the A inputs is greater than the value of the B inputs.
= Equal to: the “OUT” output is logic “1” as long as the value of the A inputs is equal to the
value of the B inputs. The “O
UT” output is set to logic “0” if the value of the A inputs is not
equal to the value of the B inputs.
!= Not equal to: the “O
UT” output is logic “1” as long as the value of the A inputs is not equal
to the value of the B inputs. The “O
UT” output is set to logic “0” if the value of the A inputs is
equal to the value of the B inputs.