PSRmodular system
76 / 232
PHOENIX CONTACT 109241_en_03
StartUp Test If this option is selected, a function test of the movable guard is required before the enable.
This test requires the movable guard to be opened in order to activate the “O
UToutput. This
check is only required on machine startup.
Filter (ms) This option enables external input signals to be filtered. The filter can be configured with a
value between 3 and 250 ms and helps suppress contact chatter. The length of the filter time
affects the calculation of the response time of the safety function.
Enable Error Out When this parameter is selected, an output (“E
RROR”) is made available which signals that
an error has been detected by the function block.
Item Description A 24-character text description of the function or the name can be entered here. The text is
displayed above the function block.