Parameter Descriptions 2-85
7000-TD002A-EN-P – September 2007
External Fault 11 Class [ExtFault11 Class]
Linear Number: 412
Default Value: Class2 Fault
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the class of the external fault 11. This is applicable only if the optional XIO board
is installed. The following options are available:
Disable This disables the fault input.
Class1 Fault The drive will shut down immediately
Class2 Fault The drive will perform a controlled shut down
Warning The drive will not shut down but a warning will be displayed
External Fault 12 Class [ExtFault12 Class]
Linear Number: 413
Default Value: Class2 Fault
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the class of the external fault 12. This is applicable only if the optional XIO board
is installed. The following options are available:
Disable This disables the fault input.
Class1 Fault The drive will shut down immediately
Class2 Fault The drive will perform a controlled shut down
Warning The drive will not shut down but a warning will be displayed
External Fault 13 Class [ExtFault13 Class]
Linear Number: 414
Default Value: Class2 Fault
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the class of the external fault 13. This is applicable only if the optional XIO board
is installed. The following options are available:
Disable This disables the fault input.
Class1 Fault The drive will shut down immediately
Class2 Fault The drive will perform a controlled shut down
Warning The drive will not shut down but a warning will be displayed
External Fault 14 Class [ExtFault14 Class]
Linear Number: 415
Default Value: Class2 Fault
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the class of the external fault 14. This is applicable only if the optional XIO board
is installed. The following options are available:
Disable This disables the fault input.
Class1 Fault The drive will shut down immediately
Class2 Fault The drive will perform a controlled shut down
Warning The drive will not shut down but a warning will be displayed