2-84 Parameter Descriptions
7000-TD002A-EN-P – September 2007
External Fault 7 Class [ExtFault7 Class]
Linear Number: 206
Default Value: Class2 Fault
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the class of the external fault 7. This is applicable only if the optional XIO board
is installed. The following options are available:
Disable This disables the fault input.
Class1 Fault The drive will shut down immediately
Class2 Fault The drive will perform a controlled shut down
Warning The drive will not shut down but a warning will be displayed
External Fault 8 Class [ExtFault8 Class]
Linear Number: 207
Default Value: Class2 Fault
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the class of the external fault 8. This is applicable only if the optional XIO board
is installed. The following options are available:
Disable This disables the fault input.
Class1 Fault The drive will shut down immediately
Class2 Fault The drive will perform a controlled shut down
Warning The drive will not shut down but a warning will be displayed
External Fault 9 Class [ExtFault9 Class]
Linear Number: 410
Default Value: Class2 Fault
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the class of the external fault 9. This is applicable only if the optional XIO board
is installed. The following options are available:
Disable This disables the fault input.
Class1 Fault The drive will shut down immediately
Class2 Fault The drive will perform a controlled shut down
Warning The drive will not shut down but a warning will be displayed
External Fault 10 Class [ExtFault10 Class]
Linear Number: 411
Default Value: Class2 Fault
Access Level: Basic
Read/Write: Read/Write
This parameter specifies the class of the external fault 10. This is applicable only if the optional XIO board
is installed. The following options are available:
Disable This disables the fault input.
Class1 Fault The drive will shut down immediately
Class2 Fault The drive will perform a controlled shut down
Warning The drive will not shut down but a warning will be displayed