Parameters Listed by Group 2-211
7000-TD002A-EN-P – September 2007
Drive Protection Parameters
Name Min. Max. Default Units
Read-
Only
Access
169 DCLnk OvrCur Trp 0.00 4.00 1.75 pu N Advanced
170 DCLnk OvrCur Dly 0 100 10 msec N Advanced
161 Line OvrCur Trp 0.00 4.00 1.75 pu N Advanced
162 Line OvrCur Dly 0 100 10 msec N Advanced
165 Line OvrVolt Trp 0.00 2.00 1.20 pu N Advanced
166 Line OvrVolt Dly 0 1000 10 msec N Advanced
173 Rec OvrVolt Trp 0.00 2.00 1.50 pu N Advanced
174 Rec OvrVolt Dly 0 100 10 msec N Advanced
193 Inv OvrVolt Trp 0.00 2.00 1.50 pu N Advanced
194 Inv OvrVolt Dly 0 100 10 msec N Advanced
271 LineVoltUnbalTrp 0.00 1.00 0.05 pu N Advanced
272 LineVoltUnbalDly 0.0 10.0 1.0 sec N Advanced
108 Line CurUnbalTrp 0.00 1.00 0.05 pu N Advanced
109 Line CurUnbalDly 0.0 10.0 1.0 sec N Advanced
167 Line UndVolt Lvl 0.40 1.50 0.85 pu N Advanced
168 Line UndVolt Dly 0 100 17 msec N Advanced
270 Drv OvrLoad Wrn 0.00 1.00 0.50 N Advanced
772 Drv Thermal Cyc 0.0 6000.0 600.0 sec N Advanced
163 Drv OvrLoad Trp 0.00 4.00 1.15 pu N Advanced
164 Drv OvrLoad Dly 0.0 600.0 60.0 sec N Advanced
269 Drv OvrLoad Min 0.00 4.00 1.05 pu N Advanced
587 LineNeutVoltTrp 0.00 1.50 0.40 pu N Advanced
588 LineNeutVoltDly 0.0 10.0 1.0 sec N Advanced
171 Gnd OvrCur Trp 0.05 10.00 0.50 A N Advanced
172 Gnd OvrCur Dly 0.0 10.0 0.1 sec N Advanced
675 Harmonic VoltTrp 0.00 10.00 0.30 pu N Advanced
676 Harmonic VoltDly 0.0 10.0 1.0 sec N Advanced
774 RNeut OvrLoadTrp 0.00 655.35 5.00 N Service
775 RNeut OvrLoadDly 0.00 655.35 2.50 sec N Service
776 RNeut OvrCurTrp 0.00 655.35 10.00 N Service
777 RNeut OvrCurDly 0.000 65.535 0.010 sec N Service
673 BusTransTrpFac 0.00 100.00 2.50 pu N Service
674 BusTransient Dly 0 100 2 N Service
677 BusTrans MinTrp 0.00 10.00 0.30 pu N Service
678 BusTrans IdcFac 0.00 10.00 0.50 pu N Service
679 Min Freewhl Time 0.000 1.000 0.016 sec N Service
698 Line Loss Trip 0.0 40.0 8.0 Hz N Service
266 Rec Dvc Diag Dly 0 6 2 N Service
268 Inv Dvc Diag Dly 0 6 2 N Service
112 RecHSink TempWrn 0 100 53 C N Service
111 RecHSink TempTrp 0 100 55 C N Service
316 InvHSink TempWrn 0 100 61 C N Service
315 InvHSink TempTrp 0 100 64 C N Service
656 IsoTx AirFlowNom 0.0 10.0 3.6 V N Service
655 IsoTx AirFlowWrn 0.0 10.0 3.0 V N Service
654 IsoTx AirFlowTrp 0.0 10.0 2.5 V N Service
317 Conv AirFlow Nom 0.0 10.0 3.6 V N Service
320 Conv AirFlow Wrn 0.0 10.0 3.0 V N Service
319 Conv AirFlow Trp 0.0 10.0 2.5 V N Service