2-212 Parameters Listed by Group
7000-TD002A-EN-P – September 2007
Motor Protection Parameters
Name Min. Max. Default Units
Read-
Only
Access
177 Mtr OvrCur Trp 0.00 4.00 1.75 pu N Advanced
178 Mtr OvrCur Dly 0 500 100 msec N Advanced
181 Mtr OvrVolt Trp 0.00 2.00 1.20 pu N Advanced
182 Mtr OvrVolt Dly 0.0 10.0 0.5 sec N Advanced
189 Mtr NeutVolt Trp 0.00 1.50 0.20 pu N Advanced
190 Mtr NeutVolt Dly 0.0 10.0 1.0 sec N Advanced
185 Mtr OvrSpeed Trp 0.0 120.0 66.0 Hz N Advanced
186 Mtr OvrSpeed Dly 0.0 2.0 0.5 sec N Advanced
179 Mtr OvrLoad Trp 0.00 4.00 1.15 pu N Advanced
180 Mtr OvrLoad Dly 0.0 600.0 60.0 sec N Advanced
350 Mtr OvrLoad Min 0.00 4.00 1.05 pu N Advanced
351 Mtr OvrLoad Wrn 0.00 1.00 0.50 N Advanced
771 Mtr Thermal Cyc 0.0 6000.0 600.0 Sec N Advanced
191 Mtr Stall Dly 0.0 10.0 2.0 sec N Advanced
585 Mtr FluxUnbalTrp 0.00 1.00 0.05 pu N Advanced
586 Mtr FluxUnbalDly 0.0 10.0 1.0 sec N Advanced
208 Mtr CurUnbal Trp 0.00 1.00 0.05 pu N Advanced
214 Mtr CurUnbal Dly 0.0 5.0 1.0 sec N Advanced
246 Mtr LoadLoss Lvl 0.00 1.00 0.25 pu N Advanced
259 Mtr LoadLoss Spd 0.0 100.0 30.0 Hz N Advanced
231 Mtr LoadLoss Dly 0.0 30.0 1.0 sec N Advanced
559 Field Loss Dly 0 60 30 sec N Service
235 Tach Loss Trip 0.0 10.0 2.0 Hz N Service
236 Tach Loss Delay 0.0 1.0 0.1 sec N Service
Sync Xfer Option Parameters
Name Min. Max. Default Units
Read-
Only
Access
298 Sync Reg Output -10.00 10.00 - Hz Y Advanced
297 Sync Reg Error -180.0 180.0 - deg Y Advanced
117 Bypass Voltage 0.000 2.000 - pu Y Advanced
159 Bypass Frequency -100.0 100.0 - Hz Y Advanced
228 Sync Error Max 0 30 0 deg N Advanced
226 Sync Lead Angle -90 90 0 deg N Advanced
227 Sync Off Delay 0.000 0.500 0.100 sec N Advanced
225 Sync Reg Gain 0.0 5.0 1.0 N Advanced
229 Sync Time 0.0 10.0 10.0 sec N Advanced
230 Sync Xfer Time 0.1 57.0 1.0 min N Advanced
763 DeSync Start Dly 1 10 1 sec N Service
Tach Option Parameters
Name Min. Max. Default Units
Read-
Only
Access
349 Tach Feedback -120.00 120.00 - Hz Y Service
233 Tach Type - - None N Basic
234 Tach PPR 120 4096 1024 PPR N Basic
644 Encoder Offset 0 360 0 deg N Advanced