344 Start teach-in
The Start teach-in parameter is used to select the signal that triggers the automatic
process for teaching in a match code.
AUTOMATIC / STATIC: A signal (e.g., a key switch) makes the reading gate open auto‐
matically. The next code read by the system is taught in as a match code.
SYSTEM TRIGGER / DYNAMIC: A signal (e.g., a key switch) at one of the sensor's digital
inputs prepares it for teaching in a match code. Once the reading gate has opened
(typically triggered by a photoelectric switch), the next code read by the system is
taught in as a match code.
345
Start delay
The Start delay parameter can be used to control when the reading window opens. The
unit can be selected via the Trigger delay parameter.
If a positive value is set, the reading gate opens at a later point, e.g., so that the sensor
only detects codes at the rear end of an object in order to reduce the decoding time.
Image capture can be tailored more precisely to the code position by adjusting the trig‐
ger.
A START DELAY (additional time/distance for which the reading gate must remain
closed after event A)
346 Station Name
A name for the PROFINET IO gateway is defined via the Station Name parameter.
The following naming conventions apply:
The station name consists of letters, digits, a dash, or a period, and must not
exceed 127 characters.
A single component of the device name, i.e., a string of characters between two
periods, must not exceed 63 characters.
With the exception of hyphens, special characters must not be used.
The device name must not start or end with a hyphen or period.
The device name must not begin with digits.
The device name must not be in the form of n.n.n.n (where n is a number between
0 and 999).
The device name must not start with the character sequence "port-xyz-" (where
x,y,z are numbers between 0 and 9).
347 Increase of decoding robustness
The settings in the Increase of decoding robustness group are used to increase the
readability of codes when the print quality is poor. However, these settings reduce the
reading reliability.
SOPAS PARAMETER OVERVIEW
114
O N L I N E H E L P | Lector62x 8013778/YPV6/2016-01-14 | SICK
Subject to change without notice

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK Lector62 Series and is the answer not in the manual?

SICK Lector62 Series Specifications

General IconGeneral
BrandSICK
ModelLector62 Series
CategoryBarcode Reader
LanguageEnglish

Related product manuals