5 Operation
5.6.2 Example of Operating with Internal Set Speeds
5-58
5.6.2 Example of Operating with Internal Set Speeds
An operating example of speed control with the internal set speeds is as shown below.
This example combines speed contro
l with the internal set speeds with the soft start function.
The shock that results when the speed is changed
can be reduced by using the soft start function.
-SPEED1
Servomotor speed
+SPEED3
+SPEED2
+SPEED1
-SPEED2
-SPEED3
0
OFF ON
Stop
/P-CL(/SPD-A)
/N-CL (/SPD-B)
/P-CON(/SPD-D)
Stop
Stop
OFF OFF OFF OFF
OFF
OFF
OFF OFF OFF OFF
OFF
ON ON ON
ON
ON ON ON
ON ON ON ON
OFF OFF OFF
Acceleration/deceleration are
done for the soft start times set in
Pn305 and Pn306.
1st speed
1st speed
2nd speed
2nd speed
3rd speed
3rd speed
Analog

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA SGDV SERVOPACK and is the answer not in the manual?

YASKAWA SGDV SERVOPACK Specifications

General IconGeneral
ModelSGDV
TypeSERVOPACK
Control ModesPosition, Speed, Torque
Communication InterfaceMECHATROLINK-II, MECHATROLINK-III, EtherCAT
Protection RatingIP20
Operating Temperature0°C to 55°C
Vibration Resistance5.9 m/s² (0.6G) at 10-60Hz
Shock Resistance49 m/s² (5G)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overload, Regenerative overload, Encoder error

Related product manuals