EasyManuals Logo

YASKAWA V1000 Series Installation & Start-Up Manual

YASKAWA V1000 Series
470 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
2.1 Section Safety
36 YASKAWA TM.V1000.01 V1000 Drive Installation & Start-Up Manual (Preliminary 01-19-07)
The speed range for continuous operation differs according to
the lubrication method and motor manufacturer.
If the motor is to be operated at a speed higher than 60 Hz, consult
with the manufacturer.
Continuously operating an oil-lubricated motor in the low-speed
range may result in burning.
When the input voltage is 480 V or higher or the wiring
distance is greater than 100 meters, pay special attention to the
motor insulation voltage or use a drive-rated motor.
Failure to comply could lead to motor winding failure.
Motor vibration may increase when operating a machine in
variable-speed mode, if that machine previously operated at a
constant speed.
Install vibration-proof rubber on the motor base or use the
frequency jump function to skip a frequency resonating the
machine.
The motor may require more acceleration torque with drive
operation than with a commercial power supply.
Set a proper V/f pattern by checking the load torque characteristics
of the machine to be used with the motor.
The rated input current of submersible motors is higher than
the rated input current of standard motors.
Select an appropriate drive according to its rated output current.
When the distance between the motor and drive is long, use a cable
thick enough to connect the motor to the drive to prevent motor
torque reduction.
NOTICE

Table of Contents

Other manuals for YASKAWA V1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 Series and is the answer not in the manual?

YASKAWA V1000 Series Specifications

General IconGeneral
ModelV1000 Series
SeriesV1000
Output Frequency0.1 to 400 Hz
Overload Capacity150% for 60 seconds
TypeAC Drive
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Output Voltage0 to Input Voltage
Power Range0.1 to 18.5 kW
Horsepower0.2 to 25 HP
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication InterfacesModbus RTU
EnclosureIP20
Ambient Temperature-10 to +50°C
Storage Temperature-20 to +60°C
Humidity5 to 95% RH (non-condensing)
Cooling MethodFan Cooled